SAFETY INFORMATIONFOR YOUR SAFETY READ BEFORE OPERATINGWARNING: If you do not follow these instructionsexactly, a fire or explosion may result causin
11 GALAXY STEAM BOILERBURNER ADJUSTMENTA.Adjust gas input rate:1. Consult gas supplier for heating value of gas (Btu/cu.ft.).2. Set thermostat high en
GALAXY STEAM BOILER 12CONTROLS, SAFETY CHECKCheck all safety controls not previously mentioned. Also, followdirections in "CARE AND MAINTENANCE&
13 GALAXY STEAM BOILERReplacement of Steam BoilersAnytime an older steam boiler is removed from the heating sys-tem and replaced with a new boiler, th
GALAXY STEAM BOILER 14C. Open the SKIMMER drain valve with caution. DO NOT open theboiler drain valve. Fill the boiler slowly until water begins to s
GALAXY STEAM BOILER 15SEQUENCE OF OPERATION FOR GALAXY STEAM BOILERSLOW WATER CUT-OFF CONTACTS CLOSED?PRESSURE CUT-OUT CONTACTS CLOSED?VENT DAMPER REL
NH2C W BA: FOR McDONNNELL & MILLER L.W.C.O. (PS-802-24) AND WATER FEEDER WF-2-U-24 ONLYJUMPERWIRE NUT41-1192 DL2S8600ORS8670PILOTLIGHTERTHERMOST
GALAXY STEAM BOILER 17WIRING DIAGRAMS FOR GXH-300HEZ STEAM BOILER OPTIONAL VENT DAMPERWIRE NUTBLUEPRESSURE CUT-OUTMALE PLUG41-1135FS8600ORS8670PILOTLI
GALAXY STEAM BOILER 18BURNERS FAIL TO OPERATECAUSE1. Safety pilot out, or flame too low.2. Gas supply valve shut off.3. Electric switch open.4. Blown
19 GALAXY STEAM BOILERIF REPLACEMENT PARTS ARE NEEDEDWhen parts are needed, refer to boiler model and serial number shownon the boiler name/rating pla
2 GALAXY STEAM BOILERORIFICE SIZES indicated for Sea Level are factory installed inboiler unless otherwise specified by the local authority.See VII, p
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LT D/LTE E, Mississauga, Ontariowww.slantf
GALAXY STEAM BOILER 3INSTALLATION REQUIREMENTSThe installation must conform to the requirements of the author-ity having jurisdiction or, in the absen
4 GALAXY STEAM BOILERB. Provide accessibility clearance of 24" on sides requiring ser-vicing and 18" on sides used for passage.C. All minimu
GALAXY STEAM BOILER 5ELECTRICAL CONTROLS AND WIRING—A. The electrical power to the boiler must be on a separatelyfused and live circuit.B. If an exter
6 GALAXY STEAM BOILERPIPING A LOW PRESSURE STEAM BOILERBoilers must be piped with good engineering practice and mustconform to the requirements of ANS
GALAXY STEAM BOILER 75. Process water applications involving steam boilers requiresthe use of heat exchangers. Any process application thatconstantly
8 GALAXY STEAM BOILERVENT DAMPER INSTALLATION The vent damper referred to in the following instructions is theSlant/Fin Corporation vent damper.This d
GALAXY STEAM BOILER 9"RECEPTACLE A" from "MALE PLUG". Remove "RECEPTACLE A" from job site and discard.2. Separate the v